Electrical tools

ElectricalTools.

Five calculators for motor current, cable sizing, power supply loading, panel heat dissipation and short-circuit current rating (SCCR). Everything runs in your browser, nothing is uploaded, and every result exports to CSV.

Tatva Logix / Engineering Tools

Motor Current Calculator

Full load current, starting current and switchgear sizing for AC and DC motors, with NEC 430 table values or IEC 60947 selection.

Nameplate values give the most accurate result. Leave the defaults for a typical 4-pole induction motor.

Full load current

-

Electrical

Protection & switchgear sizing

Formula reference: how this result is derived

Every value on the right comes from one of the expressions below. P is rated shaft output, V the line voltage, pf the power factor and η the efficiency as a decimal.

Full load current, 3-phase AC

I = (P × 1000) ÷ (√3 × V × pf × η)

Line current. √3 = 1.7321. For 7.5 kW at 415 V, 0.86 pf, 90% efficiency: 13.5 A.

Full load current, 1-phase AC

I = (P × 1000) ÷ (V × pf × η)

V is the phase-to-neutral voltage for a single-phase load.

Full load current, DC

I = (P × 1000) ÷ (V × η)

No power factor term on a DC supply.

Power unit conversion

P[kW] = HP × 0.746
HP = P[kW] ÷ 0.746

1 HP = 745.7 W. Nameplate HP is output, not input.

Apparent and reactive power

S[kVA] = √3 × V × I ÷ 1000
P[kW] = S × pf

Drop √3 for single phase. Input kW = output kW ÷ η.

Starting current

Istart = IFL × k

k: 6 to 8 direct on line, 2.2 star-delta, 3 soft starter at 300% limit, 1.5 on a VFD.

Overload relay setting

IOL = 1.15 to 1.25 × Inameplate

IEC 60947-4-1 class 10 for a standard duty cycle. NEC 430.32 sets 115 to 125% of nameplate FLA.

Conductor and protection

Icable ≥ 1.25 × IFL

NEC 430.22. Short-circuit protection to NEC 430.52 (inverse-time breaker up to 250% of FLC); under IEC follow the manufacturer type 2 coordination chart.

Torque and speed

T[N·m] = 9550 × P[kW] ÷ n[rpm]
nsync = 120 × f ÷ poles

Slip is the difference between synchronous and nameplate speed.

NEC table current

FLC from NEC Table 430.250

In NEC mode conductors and protection are sized from the table FLC, not the nameplate current. The nameplate value is used only for the overload element.

Indicative results for preliminary sizing and reference only. Verify against the applicable standard, product data and site conditions before design or procurement.

Discuss a Project
Indicative results for preliminary engineering and reference only. Verify against the applicable standard, product data and site conditions before design, procurement or issue to a customer.